overhead aerial bundled cable

Aerial Bundle Cable (ABC cable) is a very innovative concept for overhead power distribution as compared to the conventional bare conductor overhead cable.

0.6/1KV AAAC/ACSR XLPE/PE Insulation twist cable AAAC conductor has been widely used in power transmission lines and electricity distribution lines with various voltage levels

[lgc_column grid=”50″ tablet_grid=”50″ mobile_grid=”100″ last=”false”]

 

[/lgc_column] [lgc_column grid=”50″ tablet_grid=”50″ mobile_grid=”100″ last=”false”]

Conductor Material: Aluminium conductor

Insulation Material: PVC / PE

Name: AAAC ACSR XLPE PE Insulation ABC twist cable

Type: Low Voltage, types of wires and cables

Standard: IEC 60227

Certificate:CE/CCC/ISO

CONTACT US

[/lgc_column]

PRODUCT DESCRIPTION

1. 0.6/1kV Overhead Cable

2. Aluminum conductor

3. XLPE /PE Insulation

4. Phase conductor+ neutral Conductor

5. IEC ICEA NFC Standard

LV Aerial Bundled Conductor (ABC) Cables

APPLICATION OF TRIPLEX ABC CABLE

Aerial Bundle Cable (ABC cable) is a very innovative concept for overhead power distribution as compared to the conventional bare conductor overhead cable.

PROPERTY SYSTEM.

Electrical Properties
rated Voltage0.6/1kV
Test Voltage 4VeffkV
minimum laying Temperature -20°C
operating Temperature -40°C~ +90°C
maximum Short-circuit Temperature 250°C
maximum Conductor Temperature 80°C
minimum Bending radius 18×OD

It provides a higher level of safety and reliability, lower power losses and ultimate system economy by reducing installation, maintenance, and operative cost.

LV Aerial Bundle Cables are designed to supply 600/1000 volt aerial service for temporary service at construction sites, as a service drop (power pole to service entrance), as a secondary cable (pole to pole) or street lighting.

This over-head cable provides reinforced insulation acc. IEC 61140 and fulfill therefore Class II acc. IEC 61140.

It is not flame retardant. But this could be if requested a change to a flame retardant cable.

STANDARD OF TRIPLEX ABC CABLE

Basic design to BS 7870 / TNB Specification(IEC 60502) / HD 626 S1 / NFC 33-209 / AS/NZS 3560-1 standards

Construction of triplex ABC cable

Conductor: Aluminium conductor, round stranded compressed (RM).

insulation: XPLE compound, UV-resistant.

Core identification: 1, 2 resp. 3 raised longitudinal ribs on the surface of the cores.

The surface of the neutral core should have at least 12 ribs for cross-sections up to 50 mm²

and a minimum of 16 ribs for cores above 50 mm². In the case of five core bundles, the

surface of the protective core should be smooth.

CONSTRUCTION PARAMETERS OF TRIPLEX ABC CABLE TNB SPECIFICATION (IEC 60502)

number of cores nominal cross Section overall diameter weight Maximum conductor Resistance Minimum Breaking Load current Rating
No.xmm2 mm kg/km Ω/Km KN A
1×16+1×25 RM 15.3 160 1,910 2,5 72
3×16+1×25 RM 19 290 1,200 4,0 107
3×25+1×25 RM 23.2 400 0,868 5,5 132
3×35+1×25 RM 25.6 500 0,641 8,0 165
3×50+1×35 RM 30 680 0,443 10,7 205
3×70+1×50 RM 34.9 920 0,320 13,7 240
3×95+1×70 RM 40.6 1270 0,253 18,6 290
3×120+1×70 RM 44.1 1510 0,206 23,2 334
3×150+1×95 RM 49.2 1870 0,164 28,7 389
3×185+1×120 RM 54.9 2340 0,125 37,2 467
3×25+1×25+1×16 RM 23.2 470 1,910 2,5 72
3×35+1×25+1×16 RM 25.6 560 1,200 4,0 107
3×50+1×35+1×16 RM 30 740 0,868 5,5 132
3×70+1×50+1×16 RM 34.9 980 0,641 8,0 165
3×95+1×70+1×16 RM 40.6 1330 0,443 10,7 205
3×120+1×70+1×16 RM 44.1 1580 0,320 13,7 240
3×150+1×95+1×16 RM 49.2 1940 0,206 23,2 334
3×185+1×120+1×16 RM 54.9 2410 1,910 2,5 72
Choose Your Language »